Follow the links below to find material targeted to the unit's elements, performance criteria, required skills and knowledge

Elements and Performance Criteria

  1. Conduct dispenser sampling processes
  2. Fuel samples are taken from dispenser for visual testing during fuelling operations in accordance with workplace procedures and regulatory requirements
  3. Conduct fueller sampling processes
  4. Additional samples are taken from fueller after defuelling operations, vehicle washing, maintenance and rain events
  5. Conduct visual check of fuel samples
  6. Sample is inspected for free water and dirt particles in accordance with workplace procedures and established manual or automated processes
  7. Water detector capsules are used to check for suspended water in accordance with manufacturer instructions and workplace procedures
  8. Results of visual checks are recorded and reported in accordance with workplace procedures and regulatory requirements
  9. Test membrane filtration (millepore sampling)
  10. Fuellers are tested independent of test rig by circulating product through delivery hose back to tank to achieve required flow rates
  11. Bonding leads are attached in accordance with workplace procedures
  12. Fueller/dispenser delivery hoses are connected to achieve a flow rate of at least 50% of rated flow of filter
  13. Hydrant dispenser lanyard is connected to pit valve and inlet hose is connected in accordance with workplace procedures
  14. Colorimetric capsule is loaded in accordance with manufacturer instructions and workplace procedures
  15. Checks are made to ensure capsule is located in housing with millepore monitor inlet facing upstream
  16. Apparatus is connected to filter outlet millepore sample connection or nozzle millepore sample point
  17. Pressure and flow rate are adjusted to workplace specifications
  18. Calorimetric test samples are drawn monthly in accordance with sampling schedules
  19. Gravimetric and microbiological tests are drawn every three months in accordance with sampling schedules, ensuring that initial sample is drawn for gravimetric test then gravimetric capsule is replaced with microbiological capsule, and another sample is drawn in accordance with workplace procedures
  20. Apparatus is disconnected and capsule is removed
  21. Gravimetric and microbiological samples are labelled and dispatched to laboratory in accordance with workplace procedures
  22. Colorimetric assessment is conducted in accordance with manufacturer instructions and workplace procedures
  23. Test results are documented in accordance with workplace procedures and regulatory requirements
  24. Measure pressure differential on filter vessels
  25. Flow through vessel into aircraft or test rig is started in accordance with workplace procedures
  26. Pressure differential at maximum flow rate obtained is read
  27. Results are analysed and recorded in accordance with workplace procedures and regulatory requirements
  28. Where differential pressure exceeds filter manufacturer recommended differential pressure at flow rates above 50% of the maximum rated flow of filter vessel, situation is reported immediately to supervisor for investigation in accordance with workplace procedures and regulatory requirements